Difference between revisions of "Install EIB Tapko"
(Created page with "The EIB / KNX bus can be accessed in multiple ways. I use a [http://www.tapko.de/sim-knx.html Tapko EIB/KNX to RS232 converter]. It requires following connections: RxD (pin 2)...") |
|||
Line 1: | Line 1: | ||
− | The EIB / KNX bus can be accessed | + | The EIB / KNX bus can be accessed via a [http://www.tapko.de/sim-knx.html Tapko EIB/KNX to RS232 converter]. |
− | + | ||
It requires following connections: | It requires following connections: | ||
RxD (pin 2), TxD (pin 3), DTR (pin 4, powers the device), Gnd (pin 5). | RxD (pin 2), TxD (pin 3), DTR (pin 4, powers the device), Gnd (pin 5). |
Revision as of 17:04, 8 December 2014
The EIB / KNX bus can be accessed via a Tapko EIB/KNX to RS232 converter. It requires following connections: RxD (pin 2), TxD (pin 3), DTR (pin 4, powers the device), Gnd (pin 5).
Before all, make sure you have installed an xPL hub and an xPL serial port device.
Contents
Install xPL EIB bridge
Download the Tapko EIB bridge script.
Move the script to xPL scripts directory:
SCRIPTS_BASE_DIR=/home/control/Documents/Controls mv xpl-eib-Tapko.pl $SCRIPTS_BASE_DIR chown control:users $SCRIPTS_BASE_DIR/*.pl chmod 775 $SCRIPTS_BASE_DIR/*.pl
Test xPL EIB bridge
The test is shown here on a Linux machine such as a BeagleBone. It has to be slightly adapted on Mac OS.
Open a first terminal window (on any machine with xPL installed) and monitor the xPL protocol:
SCRIPTS_BASE_DIR=/home/control/Documents/Controls $SCRIPTS_BASE_DIR/xpl-monitor.pl -vf
If the xPL serial port device isn't running, launch it in a second window:
su control SCRIPTS_BASE_DIR=/home/control/Documents/Controls ll /dev/ttyO* $SCRIPTS_BASE_DIR/xpl-serial_port.pl -h $SCRIPTS_BASE_DIR/xpl-serial_port.pl -v -n eib -e '\x0A\x0D' /dev/ttyO1 baudrate 9600 databits 8 parity none stopbits 1 handshake none
Open a further terminal window and start the xPL EIB bridge:
SCRIPTS_BASE_DIR=/home/control/Documents/Controls $SCRIPTS_BASE_DIR/xpl-eib-Tapko.pl -v -n home -s dspc-serPort.eib -v
Open yet another terminal and send a message to the EIB bridge:
su control SCRIPTS_BASE_DIR=/home/control/Documents/Controls $SCRIPTS_BASE_DIR/xpl-send.pl -v -t cmnd -d dspc-eib.home -c eib.basic group='1/1/1' data=0x01
This should turn on EIB device 1/1/1
.
The monitor window should show how the EIB budge message triggered a serial port message
for the Tapko EIB/KNX to RS232 converter.
Launch the xPL serial port device at startup
The EIB bridge is to be launched after the xPL serial port device which in turn is to be launched after the xPL hub.
Installing the serial port device to launch at system boot is described in the xPL serial port page.
Ubuntu
On Ubuntu, the xPL serial port device emits xpl-eibSerialPort_started
at startup.
This will be used to state-up the xPL EIB bridge.
Edit /etc/init/xpl-eib.conf
:
################################################################################ # xPL EIB bridge, interfaves to a Tapko serial port # description "xPL EIB bridge" version "1.0" author "Francois Corthay" #------------------------------------------------------------------------------- # Configuration variables # env SCRIPTS_DIR='/home/control/Documents/Controls' env SCRIPT_NAME='xpl-eib-Tapko.pl' env PARAMETERS='-n home -s dspc-serPort.eib' #------------------------------------------------------------------------------- # Start and stop conditions # start on xpl-eibSerialPort_started stop on shutdown respawn setuid control setgid users #------------------------------------------------------------------------------- # Start daemon # exec $SCRIPTS_DIR/$SCRIPT_NAME $PARAMETERS
Start the device and test it:
su root service xpl-eib status initctl emit xpl-eibSerialPort_started service xpl-eib status SCRIPTS_BASE_DIR=/home/control/Documents/Controls $SCRIPTS_BASE_DIR/xpl-send.pl -v -t cmnd -d dspc-eib.home -c eib.basic group='1/1/1' data=0x01 $SCRIPTS_BASE_DIR/xpl-send.pl -v -t cmnd -d dspc-eib.home -c eib.basic group='1/1/1' data=0x00
Reboot the PC and check for the daemons:
ps ax | grep -i xpl | grep -v grep initctl list | grep xpl
Mac OS
On Mac OS, the xPL EIB bridge starts-up later than the xPL serial port.
Edit /Library/LaunchDaemons/eib.plist
:
<?xml version="1.0" encoding="UTF-8"?> <!DOCTYPE plist PUBLIC "-//Apple//DTD PLIST 1.0//EN" "http://www.apple.com/DTDs/PropertyList-1.0.dtd"> <plist version="1.0"> <dict> <key>Label</key> <string>xPL EIB bridge</string> <key>OnDemand</key> <false/> <key>UserName</key> <string>control</string> <key>ProgramArguments</key> <array> <string>/Users/control/Documents/Controls/xpl-eib-Tapko.pl</string> <string>-n</string> <string>home</string> <string>-s</string> <string>dspc-serPort.eib</string> <string>-w</string> <string>30</string> </array> </dict> </plist>
Start the device and test it:
su root launchctl load /Library/LaunchDaemons/xpl-eib.plist SCRIPTS_BASE_DIR=/Users/control/Documents/Controls $SCRIPTS_BASE_DIR/xpl-send.pl -v -t cmnd -d dspc-eib.home -c eib.basic group='1/1/1' data=0x01 $SCRIPTS_BASE_DIR/xpl-send.pl -v -t cmnd -d dspc-eib.home -c eib.basic group='1/1/1' data=0x00
Reboot the Mac and check for the daemons:
ps ax | grep -i xpl | grep -v grep launchctl list | grep xPL